24-ICM1503

Oil Primary, Intermittent Ignition, flame sensing circuit, 45 sec, safety switch, reset button

Out of Stock

Controls oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat. Solid state flame sensing circuit . LED on terminal strip indicates system lockout. Enclosed safety switch with external reset button. Mounts on standard 4″ x 4″ junction box select models may be mounted directly on burner housing. 69-45610 Cadmium Sulfide Flame Detector and 24 VAC thermostat required. Direct replacement for popular competitive models.

Ignition Type: Intermittent Timing, Safety Switch: 15, 30 or 45 seconds. Mounting Bracket: For mounting on a standard 4″ × 4″ junction box or direct mounting on burner housing. Electrical Rating Contacts (full load): 7.4 A @ 120 VAC 3.7 A @ 240 VAC | Electrical Rating Contacts (locked rotor): 44.4 A @ 120 VAC 22.2 A @ 240 VAC. Dimensions: 4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in. deep | 111 mm high x 104 mm wide x 64 mm deep. Temperature Range: -30°F to +130°F. Approvals – Underwriters Laboratories Inc.

 

Additional information

Cross Reference

48245

HS Code Country Of Origin NAFTA Preference Criterion NAFTA Producer Index
0__